High Voltage Insulation Tester MS5215
A insulation resistance tester that can be used in different situations when it is necessary to determine the condition of the insulation of the wires.
Presentation
This meter is an insulation resistance tester with broad range of measurement which can be applied to various situations from low-voltage to high-voltage measurements. For example, measuring the insulation of high-voltage receiving station and transformer substation, as well as the electric motor and cable.
Briefly about the product
MS5215
6хLR14 / 6x1.2V AA / 100V~240V
284x230x125mm
2426 g
CE / ETL / RoHS
CAT III 1000V / CAT IV 600V
Accessories included
Temperature Sensor
Tester probes leads: 3 x 3m (Red,Black,Blue)
Alligator Clips
Software CD
USB interface Cable
Carry bag
Battery and User's manual
Certificates
Range of measurements
Specifications
Range
Resolution
Accuracy
DC Voltage
Test ±(50V~1000V)
Input Resistance Approx. 10MΩ
Input Resistance Approx. 10MΩ
±(5%+5)
AC Voltage
Test ±(50V~750V), (50Hz~60Hz)
Input Resistance Approx. 10MΩ
Input Resistance Approx. 10MΩ
±(5%+5)
Operating Voltage 250VDC
0.01MΩ~2.5GΩ
2.51GΩ~250GΩ
2.51GΩ~250GΩ
±(5%+5)
±(20%+10)
±(20%+10)
Operating Voltage 500VDC
0.01MΩ~5.0GΩ
5.01GΩ~500GΩ
5.01GΩ~500GΩ
±(5%+5)
±(20%+10)
±(20%+10)
Operating Voltage 1000VDC
0.01MΩ~10GΩ
10.01GΩ~500GΩ
501GΩ~999GΩ
10.01GΩ~500GΩ
501GΩ~999GΩ
±(5%+5)
±(20%+10)
±(30%+20)
±(20%+10)
±(30%+20)
Operating Voltage 2.5kV DC
0.01MΩ~25GΩ
25.1GΩ~500GΩ
501GΩ~999GΩ
1TΩ~2.5TΩ
25.1GΩ~500GΩ
501GΩ~999GΩ
1TΩ~2.5TΩ
±(5%+5)
±(20%+10)
±(30%+20)
±(30%+40)
±(20%+10)
±(30%+20)
±(30%+40)
Operating Voltage 5kV DC
0.01MΩ~50GΩ
50.1GΩ~500GΩ
501GΩ~999GΩ
1TΩ~5TΩ
50.1GΩ~500GΩ
501GΩ~999GΩ
1TΩ~5TΩ
±(5%+5)
±(20%+10)
±(30%+20)
±(30%+40)
±(20%+10)
±(30%+20)
±(30%+40)
Leakage Current
10nA (1.00nA~9.99nA)
100nA (9.0nA~99.9nA)
1000nA (100nA~999nA)
10μA (0.90μA~9.99μA)
100μA (9.0μA~99.9μA)
1000μA (90μA~999μA)
3mA (0.90mA~3.00mA)
100nA (9.0nA~99.9nA)
1000nA (100nA~999nA)
10μA (0.90μA~9.99μA)
100μA (9.0μA~99.9μA)
1000μA (90μA~999μA)
3mA (0.90mA~3.00mA)
±(15%+1nA)
±(15%+5)
±(2.5%+5)
±(2.5%+5)
±(2.5%+5)
±(2.5%+5)
±(2.5%+5)
±(15%+5)
±(2.5%+5)
±(2.5%+5)
±(2.5%+5)
±(2.5%+5)
±(2.5%+5)
Resistance
0Ω~100MΩ, <85% RH, 23℃ ±5℃ / 73℉ ±9℉
101Ω~20GΩ, <75% RH, 23℃ ±5℃ / 73℉ ±9℉
101Ω~20GΩ, <75% RH, 23℃ ±5℃ / 73℉ ±9℉
501GΩ~5TΩ, <55% RH, 23℃ ±5℃ / 73℉ ±9℉
101Ω~20GΩ, <75% RH, 23℃ ±5℃ / 73℉ ±9℉
101Ω~20GΩ, <75% RH, 23℃ ±5℃ / 73℉ ±9℉
501GΩ~5TΩ, <55% RH, 23℃ ±5℃ / 73℉ ±9℉
Temperature
-10℃~0℃
0℃~40℃
40℃~70℃
0℃~40℃
40℃~70℃
±1.5℃
±2.0℃
±1.5℃
±2.0℃
±1.5℃
Features
Display
LCD
Data Logging
Up to 100 manually tested data and 10 groups
APO
Auto Power Off
Yes
Clock
Yes
AVG
Yes
PI / DAR
Polarization Index / Dielectric Absorption Ratio
Yes
Battery Capacity Indicator
Yes
Display Backlight
Yes
USB interface
Yes
Applicability
- In installers
- Insulation Diagnosis - PI and DAR can be automatically calculated and displayed
- In case of grounding of electrical installations
- For safety when installing electrical installations and equipment in an industrial environment
Working specifications
Voltage (V)
Voltage(symbol: V), also called electromotive force, is a quantitative expression of the potential difference in charge between two points in an electrical field.
Resistance (R)
Resistance is the opposition that a substance offers to the flow of electric current. It is represented by the uppercase letter R. The standard unit of resistance is the ohm(Ω)
Auto Power Off
Auto Power Off function shutting down the device after a certain inactivity time.
Display Backlight
Rear screen illumination is an important advantage for any device that owns it. Thanks to it, the visibility and legibility of the screen is increased, thus the device is much more subtle and reliable in small ambient light and long-term use.
Data Hold
Data hold function is useful when measurements occur. So when pressing the "HOLD" button you will hold the display information.
USB interface
The USB interface allows the device to be connected to other devices and thus enables the exchange of data and values of the measured quantities.
Average value
AVG function shows the average of the measurements.
Data Logging
This feature allows you to store measurement data in your device.
Tenperature (°C)
Temperature measurement is done in degrees (°). The unit of measurement adopted by the SI system is Celsius (° C), the freezing point of water is 0 ° C and the boiling point is 100 ° C.
Dielectric Absorption Ratio
Dielectric Absorption Ratio
Polarization Index
Automatic calculation of Polarization Index
Battery Indicator
The device has an Battery capacity indicator.
Clock
The device has a clock to display or measure the time.
Brochures and instructions